FCT18-BD Industrial Double Interval Time Relay

Dual Timing Control with Control Signal Functionality

Model: FCT18-BD Series | DIN Rail Mount

Product Overview

The FCT18-BD is a sophisticated double interval time relay with control signal functionality, engineered for complex industrial timing applications. This relay provides two precise timing intervals triggered by the application and removal of the control signal. With its compact 18mm DIN rail design, universal voltage input (12-240V AC/DC), and exceptional accuracy (±0.1%), the FCT18-BD delivers reliable dual-timing control for demanding industrial automation systems.

Key Technical Advantages

Universal Voltage Input

Operates with 12-240V AC/DC, compatible with global industrial power standards.

Dual Timing Intervals

Provides two independent timing sequences controlled by signal application and removal.

Ultra-Compact Design

Space-saving 18mm width (90×18×64mm) for high-density control panels.

Exceptional Accuracy

Repeat accuracy ∆< ±0.5% and Time setting accuracy ∆< ±0.1%.

Industrial Robustness

Designed for -20°C to +60°C environments with EMI resistance.

Flexible Triggering

Supports NPN or PNP input options for versatile integration.

High-Capacity Output

16A C/O contacts (1 or 2 sets) for industrial loads.

Button Setting & Locking

Precision time setting via tactile buttons with locking protection to prevent accidental changes.

Industrial Application Scenarios

The FCT18-BD double interval relay excels in scenarios requiring two distinct timing sequences triggered by control signal application and removal. Below are key applications where its dual-timing functionality delivers superior performance:

Equipment Cooling Systems

Applies cooling immediately after shutdown (T1) and activates secondary cooling phase (T2) after equipment cools to safe levels.

Key Benefits:

  • Optimizes cooling efficiency with dual-phase approach
  • Prevents thermal shock by staging cooling intensity
  • Reduces energy consumption by 25%

Automated Assembly Lines

Controls primary assembly sequence (T1) when activated and secondary inspection sequence (T2) when deactivated.

Key Benefits:

  • Coordinates complex multi-stage processes
  • Ensures quality control after assembly
  • Reduces cycle time by 15%

Safety Lockout Systems

Activates primary safety lock (T1) immediately and secondary verification lock (T2) after personnel clearance.

Key Benefits:

  • Two-stage safety confirmation
  • Prevents accidental reactivation during maintenance
  • Complies with ISO 13849 safety standards

Chemical Dosing Systems

Controls primary chemical injection (T1) when activated and neutralizing agent (T2) when deactivated.

Key Benefits:

  • Precise chemical reaction control
  • Automated neutralization for safety
  • Reduces waste by 30%

Water Treatment Systems

Activates primary filtration (T1) when enabled and backwash cycle (T2) when disabled.

Key Benefits:

  • Automated filter maintenance cycle
  • Optimized water treatment efficiency
  • Extended filter lifespan

Conveyor Sequencing

Starts primary transport (T1) when activated and secondary positioning (T2) when deactivated.

Key Benefits:

  • Precise material positioning
  • Reduced product damage
  • Throughput increase of 20%

Timing Sequence

fct18-bd-function-diagram

Dual-Timing Operation:

1
Control signal (S) applied – output (R) closes and timing starts
2
After preset time (T) – output (R) opens
3
Output (R) closes again when control signal (S) removed
4
After preset time (T) – output (R) opens

Wiring Diagram

fct18-bd-wiring-diagram

Connection Guide:

Standard DIN rail mounting with screw terminals for secure industrial connections:

  • A1/A2: Power supply terminals (12-240V AC/DC)
  • S: Control signal input
  • 11/12/14 & 21/22/24: Output contacts (C/O)
  • T1/T2: Timing interval adjustment

Parameter Setting

time-setting-diagram

Time Adjustment Protocol:

1
To set new parameters, press and hold the button until the LED starts flashing.
2
Adjust the timing parameters to desired values using the adjustment buttons.
3
Press and hold the button until the LED stops flashing to save settings.
4
For the new settings to take effect, power cycle the device.

Technical Specifications

Parameter FCT18-BD1 FCT18-BD2
Input terminal A1-A2
Voltage range AC230V / DC24V / ACDC12-240V
Voltage tolerance -15% ~ +10%
Output type 1 C/O contact 2 C/O contacts
Rated current 1×16A 2×16A
Power consumption AC 3.5VA / DC 2.0W
Time delay setting accuracy ±0.1% of full-scale value
Repeat accuracy Δt < ±0.5%
Mechanical life 10 million operations
Electrical life 100,000 operations
Ambient temperature -20°C to +60°C
Mounting DIN rail EN/IEC 60715
IP rating IP20
Dimensions 90×18×64mm
Standards IEC60947-5-1, EN6812-1
IEC 60947-5-1 Compliant
CE Certified
RoHS Compliant
IP20 Protection