FIICCO FCL18-01 Liquid Level Relay
FIICCO Industrial Relay

FCL18-01

Single‑Function Liquid Level Relay | Dual‑Probe Emptying Control | 18mm DIN Rail

2 polesEmptying control
AC/DCWide range
16AContact rating
1 modeFixed function
18mmDIN rail
CE Certified
RoHS Compliant
IEC 60947-5-1
GB/T 14048.5
EN 61812-1

Dedicated Dual‑Level Emptying Control in 18mm Width

The FCL18-01 is a specialized liquid level relay designed exclusively for dual‑level emptying control applications. Engineered for reliability in industrial environments, this relay activates the pump when liquid reaches the high level and continues pumping until the low level is reached. Its focused functionality ensures optimal performance in drainage, tank emptying, and wastewater systems.

With a compact 18mm DIN‑rail housing, AC/DC 12‑240V wide supply range, and a robust 16A SPDT output, the FCL18‑01 offers a cost‑effective solution for applications requiring reliable high‑level to low‑level pump‑down control.

Key Advantage: Dedicated dual‑probe emptying control with built‑in dry‑run protection — prevents pump damage when liquid level is too low. Simple sensitivity adjustment via front‑panel button, no mode selection or time delay required.

Quick Specifications

Supply VoltageAC/DC 12‑240V
Power ConsumptionAC 3.5VA / DC 2.0W
Control ModeEmpty Liquid with 2 Levels
Sensitivity Range10kΩ – 100kΩ (adjustable)
Output Contact1 × SPDT (NO+NC)
Rated Current16A / 250V AC
Mechanical Life1 × 10⁷ operations
Electrical Life1 × 10⁵ operations
MountingDIN rail EN/IEC 60715 (35mm)
Dimensions (H×W×D)90 × 18 × 64 mm
Weight68g

Why Choose the FCL18-01?

Engineered for reliable dual‑level emptying control in industrial environments.

Dedicated Emptying Control

Single‑function relay optimized for dual‑level pump‑down applications — activates at high level, deactivates at low level.

Adjustable Sensitivity

Fine‑tune the detection threshold (10–100kΩ) to match different probe lengths and liquid conductivity.

16A SPDT Relay

Directly switch pumps, valves, or alarms. Mechanical life up to 10 million cycles.

Simple One‑Button Setup

Single button for sensitivity adjustment. No mode selection or time delay configuration required.

Wide AC/DC Supply

Universal 12–240V AC/DC input – one model works for global installations without modifications.

Dual‑Level Emptying Control

The FCL18-01 operates exclusively in 2‑level control, providing precise control for emptying operations using two level sensors.

Mode F – Dual‑Level Emptying Control

This specialized relay activates the pump when the liquid reaches the high‑level sensor (S1) and continues pumping until the liquid drops below the low‑level sensor (S2). Ideal for applications requiring complete tank emptying with pump protection.

  • High‑Level Trigger: Pump activates when liquid reaches or exceeds the HIGH level (S1)
  • Continuous Operation: Pump remains active while liquid level is above LOW level (S2)
  • Low‑Level Shutoff: Pump deactivates when liquid drops to or below LOW level (S2)
  • Built‑in Protection: Prevents pump dry‑running and ensures complete tank emptying
FCL18-01 Function Diagram – Dual-Level Emptying Control
FCL18-01 – Dual‑Level Emptying Control Function Diagram

Technical Specifications

ParameterSpecification
Supply VoltageAC/DC 12‑240V (-15% / +10%)
Power ConsumptionAC 3.5VA / DC 2.0W
Supply IndicationGreen LED (Un)
Relay IndicationRed LED (R)
Control ModeEmpty Liquid with 2 Levels (fixed)
Probe Configuration2 probes only (S1, S2, C)
Sensitivity Setting10kΩ – 100kΩ (adjustable via button)
Output Contact1 × SPDT (NO+NC)
Rated Current16A / 250V AC
Mechanical Life1 × 10⁷ operations
Electrical Life1 × 10⁵ operations
Ambient Temperature-20°C … +60°C
Storage Temperature-40°C … +85°C
MountingDIN rail EN/IEC 60715 (35mm)
Dimensions (H×W×D)90 × 18 × 64 mm
Weight68g
IP RatingIP20
StandardsGB/T 14048.5, IEC 60947‑5‑1, EN 61812‑1

Terminal Connections

FCL18-01 – Dual‑Level Emptying Control Wiring

A1
Power supply input (AC L / DC +)
A2
Power supply neutral (AC N / DC −)
11
Relay Common (C)
12
Relay Normally Closed (NC)
14
Relay Normally Open (NO)
S1
High level probe (pump starts when liquid reaches this point)
S2
Low level probe (pump stops when liquid drops below this point)
C
Common probe (reference electrode)
Wiring Safety Checklist
  • De‑energize the panel before wiring.
  • Verify supply voltage matches AC/DC 12‑240V rating.
  • Connect the load (pump/valve) between terminal 11 and 14 (NO) for normal operation.
  • For dual‑probe emptying control, connect probes to S1 (high), S2 (low), and C (common).
  • Use correct wire gauge for 16A load (min 1.5mm²).
  • Tighten screws to 0.4 N·m; stripping length 7mm (AWG13‑20).

Front Panel & Settings

Configure sensitivity using the front‑panel button – no mode selection or time delay required.

Un – Green LED

Lit = power supply applied

R – Red LED

Lit = relay output active (NO closed, pump running)

How to Adjust Sensitivity

  1. Enter setting mode: Press and hold the Sensitivity button until the green LED starts flashing.
  2. Adjust sensitivity: Continue pressing the button to cycle through sensitivity levels (10kΩ, 20kΩ, 50kΩ, 100kΩ). The red LED blinks to indicate the selected level.
  3. Confirm & exit: Press and hold the button again until the green LED stops flashing. The setting is saved.

Note: The FCL18-01 has a fixed emptying control mode. No function selection or time delay adjustment is available – simply set the sensitivity and the relay is ready for operation.

Model Comparison

ModelFunctionProbe PolesModesSensitivityDelay
FCL18-01Single‑function emptying control2 poles only1 (Emptying)Adjustable 10‑100kΩNot available
FCL18-02Multifunction level relay1 or 2 poles6 (A‑F)Adjustable 10‑100kΩ0.1‑20s
* FCL18-01 is a cost‑optimized version for basic 2‑probe emptying applications. For applications requiring fill control, 1‑probe operation, or adjustable time delays, choose the FCL18-02.

Product Video

Typical Applications

Wastewater Systems

Control pumps in sewage treatment and drainage systems.

Industrial Tanks

Empty chemical storage and processing tanks.

Fuel Storage

Control fuel transfer between storage tanks.

Chemical Processing

Precise emptying of reaction vessels.

Ready to Order or Need More Details?

Download the datasheet or contact FIICCO for pricing, samples, and OEM options.

Frequently Asked Questions

FCL18-01 is a single‑function relay dedicated to dual‑probe emptying control with adjustable sensitivity only. FCL18-02 is a multifunction relay with 6 selectable modes (A–F), adjustable sensitivity, and adjustable time delay.

Connect the common reference electrode to terminal C. Connect the high‑level probe to S1 (pump starts when liquid reaches this point) and the low‑level probe to S2 (pump stops when liquid drops below this point). For dual‑probe emptying control, all three probes are required.

The FCL18-01 accepts AC/DC 12–240V (‑15% / +10%). One model works for 12V, 24V, 110V, 230V AC or DC systems.

No. The FCL18-01 is a simplified single‑function relay with only sensitivity adjustment. For applications requiring time delay, please use the FCL18-02 multifunction model.

The SPDT output relay is rated 16A at 250V AC (resistive load), suitable for direct control of pumps, contactors, and valves.

Yes. We provide custom branding, model numbering, packaging, and tailored specifications for volume orders. Contact us for details.