FCP18-04 Series

Phase Control Relay
Adjustable Asymmetry & Fixed 5s Delay

Versatile three-phase monitoring with adjustable asymmetry (5%–15%), user-configurable over/under voltage thresholds (2%–20%), and a fixed 5-second time delay — designed for comprehensive protection of motors and sensitive industrial equipment.

3×208–480V AC L-L Phase Loss + Sequence Over/Under Voltage Adj. Asymmetry 5%–15% Adj. Fixed 5s Time Delay DIN rail mount 18mm slim design 1×SPDT 16A @ 250V AC LED Status Indication IP40 Front
FCP18-04 Phase Relay with Adjustable Asymmetry
🎚️ 5–15% Adjustable Asymmetry Fine-tune the imbalance trip threshold from 5% to 15% to match motor sensitivity and application requirements.
🎯 ±2–20% Adjustable Voltage Thresholds Independent overvoltage (2%–20%) and undervoltage (-20%–-2%) settings for precise grid protection.
⏱️ 5s Fixed Time Delay Built-in 5-second delay prevents nuisance tripping during momentary fluctuations — no adjustment needed.
💡 Comprehensive LED Indication Dedicated LEDs for power (Un), phase status (P), relay output (R), overvoltage, undervoltage, and asymmetry.
🛡️ Enhanced Anti-EMI Design Stable and accurate measurement in electromagnetically noisy industrial environments.
🔧 1×10⁷ Mechanical Life Exceptional durability with 1×10⁷ mechanical operations for demanding applications.

📋 Models & Ordering

Model System Type Supply Voltage Terminals Protection Functions Datasheet
FCP18-04A 3-phase 3-wire (L-L) 173–275V AC L1 – L2 – L3 Phase Loss + Seq. + OV/UV + Asym. (5-15%) 📄 Download PDF
FCP18-04B 3-phase 4-wire (L-N) 100–160V AC L1 – L2 – L3 – N Phase Loss + Seq. + OV/UV + Asym. (5-15%) 📄 Download PDF
FCP18-04C 3-phase 3-wire (L-L) 310–480V AC L1 – L2 – L3 Phase Loss + Seq. + OV/UV + Asym. (5-15%) 📄 Download PDF
FCP18-04D 3-phase 4-wire (L-N) 180–278V AC L1 – L2 – L3 – N Phase Loss + Seq. + OV/UV + Asym. (5-15%) 📄 Download PDF

💡 Model selection guide: Choose A/C for 3-phase 3-wire (L-L) systems, or B/D for 3-phase 4-wire (L-N) systems. All models provide Phase Loss, Phase Sequence, adjustable Over/Under Voltage (2%–20%), adjustable Asymmetry (5%–15%), and a fixed 5-second time delay.

⚙️ Technical Specifications

🔌 Input — Measuring (All Models)

Supply Terminal (A/C)L1 – L2 – L3
Supply Terminal (B/D)L1 – L2 – L3 – N
Monitoring TerminalSame as supply terminal
Supply Voltage (A)173–275V AC L-L
Supply Voltage (B)100–160V AC L-N
Supply Voltage (C)310–480V AC L-L
Supply Voltage (D)180–278V AC L-N
Supply Frequency45–60Hz

🛡️ Monitoring Function

Phase Failure✔ (Response < 200ms)
Phase Sequence✔ (Response < 500ms)
Overvoltage2%–20% adjustable
Undervoltage-20%–-2% adjustable
Asymmetry5%–15% adjustable
Time Delay5s fixed

🔌 Output

Contact1 × SPDT
Rated Current16A @ 250V AC
Mechanical Life1×10⁷ operations
Electrical Life1×10⁵ operations

📐 Physical & Environmental

Dimensions18 × 90 × 64 mm
MountingDIN rail EN 60715
Protection DegreeIP40 (front) / IP10 (terminals)
Operating Temp.-20°C ~ +55°C
Storage Temp.-30°C ~ +70°C

📜 Standards & Certifications

ComplianceGB/T 14048.5, IEC 60947-5-1, EN 6812-1
Contact ConfigurationSPDT: 11(COM)-12(NC)-14(NO)
Pollution Degree2
Max. Cable SizeAWG 13–20 / 0.4 N·m
Setting Deviation0% – Digital Setting

💡 Panel LED Indicators

LED Color Status Meaning
Un Green OFF Supply voltage not applied
Un Green ON Supply voltage applied
P Red ON Phase normal (correct sequence, all phases present)
P Red Flashing Phase sequence error
P Red OFF Phase loss detected
R Red OFF NC (11-12) contact closed
R Red ON NO (11-14) contact closed

📈 Function Diagram – Phase Loss & Sequence Protection

FCP18-04 Phase Loss and Phase Sequence Protection

• The relay continuously monitors the three-phase supply connected to L1-L2-L3 (and N for 4-wire models).
• When all three phases are present and in correct sequence, the output relay R closes after the fixed 5-second delay. The P LED stays ON.
• If a phase loss is detected, the output relay R opens immediately (within 200ms). The P LED turns OFF.
• If a phase sequence error is detected, the output relay R opens immediately. The P LED flashes.
• When the fault clears, the relay automatically re-closes after the 5-second re-energization delay.

📈 Function Diagram – Overvoltage & Undervoltage Protection

FCP18-04 Overvoltage and Undervoltage Protection

• The relay continuously monitors voltage against the set overvoltage threshold (2%–20%) and undervoltage threshold (-20%–-2%).
• If voltage goes above the overvoltage threshold, the output relay R opens after the fixed 5-second delay. Once voltage returns below the threshold, R automatically re-closes.
• If voltage drops below the undervoltage threshold, the output relay R opens after the fixed 5-second delay. Recovery above the threshold automatically re-closes R.
• The 5-second delay prevents nuisance tripping from short voltage spikes or dips.

📈 Function Diagram – Asymmetry (Phase Imbalance) Protection

FCP18-04 Asymmetry Protection Function Diagram

• The relay calculates the voltage asymmetry percentage between the three phases.
• When asymmetry exceeds the user-set threshold (5%–15%), the output relay R opens after the fixed 5-second delay.
• If asymmetry drops back below the set threshold, the output relay automatically re-closes.
• Adjustable asymmetry protection is essential for preventing motor overheating and damage caused by unbalanced supply voltages.

🎬 See it in Action

🔧 Wiring & Terminal Layout

Terminal Identification

L1 — Phase L1 L2 — Phase L2 L3 — Phase L3 N — Neutral (B/D only) 11 — COM 12 — NC 14 — NO
⚠️ Safety Note: Keep the power supply disconnected during the entire installation process. Carefully check the wiring diagram and follow it correctly. Adhere to the specified voltage and current limits for each connection terminal.

3-phase 3-wire models (A/C): Connect L1, L2, L3 directly. No neutral connection required.
3-phase 4-wire models (B/D): Connect L1, L2, L3, and N. The wiring diagram shown is for 4-wire models. For 3-wire models, simply omit the N terminal.

FCP18-04 Wiring and Terminal Layout Diagram (4-wire L-N configuration)

Shown: 4-wire (L-N) wiring for B/D models. For A/C models, omit the N terminal.

🛠️ Parameter Setting Guide

  1. Enter Parameter Setting Mode: Press and hold the button until the LED starts flashing. This indicates you have entered the configuration mode.
  2. Set Rated Voltage (Un): Use the button to set the correct input voltage for your three-phase system. Available options are shown on the front panel scale.
  3. Set Overvoltage (U>) & Undervoltage (U<) Rate: Configure the overvoltage threshold (2%–20%) and undervoltage threshold (-20%–-2%).
    💡 Note: When setting over & under voltage range, if the green LED is ON, add +1% to the scale reading for accurate threshold setting.
  4. Set Asymmetry (Asy) Threshold: Choose the desired asymmetry trip point from 5% to 15% using the dedicated scale. This determines the maximum allowable voltage imbalance before the relay trips.
  5. Confirm and Store: After all parameters are adjusted, press and hold the button until the LED stops flashing. The settings are stored and take effect immediately. The time delay is fixed at 5 seconds and does not require configuration.

🏭 Typical Applications

Critical Motor Protection
Adjustable asymmetry to match motor sensitivity — prevents overheating from phase imbalance
🌀 Industrial Compressors
Protects scroll, screw and reciprocating compressors from voltage faults and sequence errors
💧 Water/Wastewater Pumps
Safeguards submersible and surface pumps from phase loss, under/over voltage and imbalance
🏭 Production Machinery
Ensures conveyors, mixers, and machine tools only operate with healthy three-phase supply
🌬️ HVAC & Climate Control
Protects chillers, cooling towers, and air handling units from power quality issues
🏢 Building Management
Monitors main three-phase feeders to prevent equipment damage from supply anomalies

🔗 Related Products

Explore other phase relays in the FCP18 series, or time relays in the FCT18 series:

❓ Frequently Asked Questions

🔹 Can I adjust the asymmetry trip level?
Yes. Unlike the FCP18-03 (fixed 8%), the FCP18-04 allows you to set the asymmetry threshold between 5% and 15% in fine increments, giving you full control over motor protection sensitivity.
🔹 How long is the time delay? Can I change it?
The time delay is fixed at 5 seconds and cannot be adjusted. This applies to all protection functions (phase sequence, under/over voltage, asymmetry). It provides a consistent balance between fast tripping and nuisance immunity.
🔹 How do I set the overvoltage and undervoltage limits?
After entering the setting mode, adjust the U> and U< scales. When the green LED is ON during setting, add 1% to the scale reading for precise thresholds. Confirm by long-pressing the button until the LED stops flashing.
🔹 What happens if the asymmetry drops below the set threshold?
Once the voltage imbalance falls below the set asymmetry percentage, the relay automatically re-closes its output contact (after the 5-second stabilization delay), restoring power to the load.
🔹 What is the mechanical life of the output contacts?
The relay has an outstanding mechanical life of 1×10⁷ operations. Electrical life is 1×10⁵ operations at rated 16A/250V AC load.
🔹 Can I use this for both 3-wire and 4-wire systems?
Yes. Simply select the appropriate sub-model: A or C for 3-phase 3-wire (L-L), B or D for 3-phase 4-wire (L-N). The relay measures voltages according to the connected terminals.