FCP18-06 Series

Phase Control Relay
All-in-One Fixed Parameter Protection

Complete three-phase monitoring with fixed parameters — ±15% over/under voltage, 8% asymmetry, and 5s delay — ready to install without any configuration. The simplest, most robust solution for standardized motor and equipment protection.

3×208–480V AC L-L Phase Loss + Sequence OV/UV ±15% Fixed Asymmetry 8% Fixed 5s Fixed Delay No Configuration Required DIN rail mount 18mm slim design 1×SPDT 16A @ 250V AC IP40 Front
FCP18-06 All-in-One Phase Control Relay
🔧 Plug & Play All parameters are factory-set — ±15% voltage, 8% asymmetry, 5s delay. Wire it up and it's ready to protect.
🛡️ ±15% Fixed Over/Under Voltage Reliable tripping at +15% overvoltage and -15% undervoltage — no settings to misconfigure.
⚖️ 8% Fixed Asymmetry Pre-configured 8% imbalance threshold provides optimal protection for standard three-phase motors.
⏱️ 5s Fixed Time Delay Built-in 5-second delay prevents nuisance tripping during momentary fluctuations — consistent and predictable.
💡 Clear LED Diagnostics Immediate visual status of power, phase condition, voltage faults, asymmetry, and relay output.
📏 1×10⁷ Mechanical Life Exceptional durability with 1×10⁷ mechanical operations for long-term reliability.

📋 Models & Ordering

Model System Type Supply Voltage Terminals Protection Functions Datasheet
FCP18-06A 3-phase 3-wire (L-L) 173–275V AC L1 – L2 – L3 Phase Loss + Seq. + OV/UV ±15% + Asym. 8% 📄 Download PDF
FCP18-06B 3-phase 4-wire (L-N) 100–160V AC L1 – L2 – L3 – N Phase Loss + Seq. + OV/UV ±15% + Asym. 8% 📄 Download PDF
FCP18-06C 3-phase 3-wire (L-L) 310–480V AC L1 – L2 – L3 Phase Loss + Seq. + OV/UV ±15% + Asym. 8% 📄 Download PDF
FCP18-06D 3-phase 4-wire (L-N) 180–278V AC L1 – L2 – L3 – N Phase Loss + Seq. + OV/UV ±15% + Asym. 8% 📄 Download PDF

💡 Model selection guide: A/C for 3-wire (L-L), B/D for 4-wire (L-N). All parameters are fixed: Overvoltage +15%, Undervoltage -15%, Asymmetry 8%, Time Delay 5s. No user configuration needed — simply connect and the relay protects your equipment automatically.

⚙️ Technical Specifications

🔌 Input — Measuring (All Models)

Supply Terminal (A/C)L1 – L2 – L3
Supply Terminal (B/D)L1 – L2 – L3 – N
Monitoring TerminalSame as supply terminal
Supply Voltage (A)173–275V AC L-L
Supply Voltage (B)100–160V AC L-N
Supply Voltage (C)310–480V AC L-L
Supply Voltage (D)180–278V AC L-N
Supply Frequency45–60Hz

🛡️ Monitoring Function (All Fixed)

Phase Failure✔ (Response < 200ms)
Phase Sequence✔ (Response < 500ms)
Overvoltage+15% fixed
Undervoltage-15% fixed
Asymmetry8% fixed
Time Delay5s fixed

🔌 Output

Contact1 × SPDT
Rated Current16A @ 250V AC
Mechanical Life1×10⁷ operations
Electrical Life1×10⁵ operations

📐 Physical & Environmental

Dimensions18 × 90 × 64 mm
MountingDIN rail EN 60715
Protection DegreeIP40 (front) / IP10 (terminals)
Operating Temp.-20°C ~ +55°C
Storage Temp.-30°C ~ +70°C

📜 Standards & Certifications

ComplianceGB/T 14048.5, IEC 60947-5-1, EN 6812-1
Contact ConfigurationSPDT: 11(COM)-12(NC)-14(NO)
Pollution Degree2
Max. Cable SizeAWG 13–20 / 0.4 N·m
SettingNone required — all factory-preset

💡 Panel LED Indicators

LED Color Status Meaning
Un Green OFF Supply voltage not applied
Un Green ON Supply voltage applied
P Red ON Phase normal (correct sequence, all phases present)
P Red Flashing Phase sequence error
P Red OFF Phase loss detected
R Red OFF NC (11-12) contact closed
R Red ON NO (11-14) contact closed

📈 Function Diagram – Phase Loss & Sequence Protection

FCP18-06 Phase Loss and Phase Sequence Protection

• The relay continuously monitors the three-phase supply connected to L1-L2-L3 (and N for 4-wire models).
• When all three phases are present and in correct sequence, the output relay R closes after the fixed 5-second delay. The P LED stays ON.
• If a phase loss is detected, the output relay R opens immediately (within 200ms). The P LED turns OFF.
• If a phase sequence error is detected, the output relay R opens immediately. The P LED flashes.
• When the fault clears, the relay automatically re-closes after the 5-second re-energization delay.

📈 Function Diagram – Overvoltage & Undervoltage Protection (±15%)

FCP18-06 Overvoltage and Undervoltage Protection

• The relay monitors voltage with fixed thresholds: +15% overvoltage and -15% undervoltage relative to the nominal input voltage.
• If voltage goes above +15% of nominal, the output relay R opens after the fixed 5-second delay. Recovery below the threshold automatically re-closes R.
• If voltage drops below -15% of nominal, the output relay R opens after the fixed 5-second delay. Recovery above the threshold automatically re-closes R.
• No configuration required — these thresholds provide balanced protection for standard industrial equipment.

📈 Function Diagram – Asymmetry (Phase Imbalance) Protection (8%)

FCP18-06 Asymmetry Protection Function Diagram

• The relay calculates voltage asymmetry between phases: Asy = (Umax - Umin) / Uavr.
• When asymmetry exceeds the fixed 8% threshold, the output relay R opens after the fixed 5-second delay.
• If asymmetry drops back below 8%, the output relay automatically re-closes.
• The 8% threshold is ideal for general-purpose motor protection, preventing overheating while avoiding unnecessary trips from minor grid imbalances.

🎬 See it in Action

🔧 Wiring & Terminal Layout

Terminal Identification

L1 — Phase L1 L2 — Phase L2 L3 — Phase L3 N — Neutral (B/D only) 11 — COM 12 — NC 14 — NO
⚠️ Safety Note: Keep the power supply disconnected during the entire installation process. Carefully check the wiring diagram and follow it correctly. Adhere to the specified voltage and current limits for each connection terminal.

3-phase 3-wire models (A/C): Connect L1, L2, L3 directly. No neutral connection required.
3-phase 4-wire models (B/D): Connect L1, L2, L3, and N. The wiring diagram shown is for 4-wire models. For 3-wire models, simply omit the N terminal.

FCP18-06 Wiring and Terminal Layout Diagram (4-wire L-N configuration)

Shown: 4-wire (L-N) wiring for B/D models. For A/C models, omit the N terminal.

🕹️ How It Works — Plug & Protect

  1. Apply Three-Phase Supply: Connect L1, L2, L3 (and N for B/D models) to the monitored supply. The green Un LED illuminates.
  2. Automatic Phase & Voltage Check: The relay verifies phase sequence and checks that voltage is within ±15% of nominal. After a 5-second delay, if all conditions are normal, the output relay R closes.
  3. Continuous Protection: The relay monitors for phase loss, sequence error, over/under voltage (±15%), and asymmetry (8%). Any fault causes the output to open after the 5-second delay (except phase loss/sequence, which trip immediately).
  4. Automatic Recovery: When the fault clears, the relay automatically re-closes after the fixed 5-second stabilization delay. No user intervention required.

🏭 Typical Applications

Standard Motor Protection
Pre-configured for general-purpose three-phase motor starters and contactors
💧 Pump Control Panels
Reliable plug-and-play protection for water, wastewater, and irrigation pumps
🌀 HVAC Equipment
Protects compressors, fans, and chillers with zero configuration needed
🏗️ Conveyor & Material Handling
Prevents reverse operation and motor damage from supply faults
🔧 OEM Machine Builders
Standardized protection across machine series — no field adjustments needed
🏢 Building Services
Fixed protection for elevator, escalator, and ventilation three-phase supplies

🔗 Related Products

Explore other phase relays in the FCP18 series, or time relays in the FCT18 series:

❓ Frequently Asked Questions

🔹 Do I need to configure any settings on the FCP18-06?
No. All protection parameters are factory-preset and fixed: Overvoltage +15%, Undervoltage -15%, Asymmetry 8%, Time Delay 5s. Simply wire the relay and it begins protecting your equipment immediately. This makes it ideal for OEMs and standardized installations.
🔹 Can I use the FCP18-06 if my voltage tolerance requirements are different?
If you need adjustable voltage thresholds, consider the FCP18-02 (over/under voltage 2%–20% adjustable) or FCP18-04 (adjustable voltage plus adjustable asymmetry). The FCP18-06 is designed for applications where ±15% is the accepted standard.
🔹 Does the 5-second delay apply to all fault types?
Phase loss and phase sequence errors cause immediate tripping (<200ms for phase loss, <500ms for sequence). The 5-second delay applies to overvoltage, undervoltage, and asymmetry faults, as well as to the initial start-up and recovery after faults clear.
🔹 How is the 8% asymmetry calculated?
Asymmetry is calculated as (Umax - Umin) / Uavr × 100%, where Uavr is the average of the three phase voltages. If the result exceeds 8%, the relay trips after the 5-second delay.
🔹 What is the mechanical life of the output contacts?
The relay has an outstanding mechanical life of 1×10⁷ operations. Electrical life is 1×10⁵ operations at rated 16A/250V AC load.