FCT18-B Series

Power Off-Delay Relay
with Control Signal

Industrial-grade time relay with digital setting, ultra-wide voltage range, and exceptional accuracy for demanding automation applications requiring delayed opening.

Wide-voltage 12–240V AC/DC 0.1s–100 days time range 0% setting deviation 0.2% repeat accuracy DIN rail mount 18mm slim design 1×SPDT / 2×SPDT 16A @ 250V AC NPN / PNP IP40 Front
FCT18-B Power Off-Delay Time Relay
🎯 0% Setting Deviation Digital button configuration eliminates the 5–10% deviation typical of potentiometer-based timers.
🔄 0.2% Repeat Accuracy Matches top international brands for consistent, reliable timing cycle after cycle.
🔒 Anti-Misoperation Lock Long-press required for reconfiguration — prevents accidental parameter changes in the field.
🛡️ Enhanced Anti-EMI Design Reinforced circuit ensures stable operation even in complex electromagnetic environments.
12–240V Wide Supply Voltage AC/DC universal — one relay covers virtually all common control voltages worldwide.
⏱️ 0.1s–100d Ultra-Wide Time Range From sub-second pulses to multi-day delays — all in a single compact unit.

📋 Models & Ordering

Model Supply Voltage Output Contact Trigger Type Control Terminal Datasheet
FCT18-B1WN 12–240V AC/DC 1 × SPDT NPN A2 – S 📄 Download PDF
FCT18-B1WP 12–240V AC/DC 1 × SPDT PNP A1 – S 📄 Download PDF
FCT18-B2WN 12–240V AC/DC 2 × SPDT NPN A2 – S 📄 Download PDF
FCT18-B2WP 12–240V AC/DC 2 × SPDT PNP A1 – S 📄 Download PDF

💡 Naming convention: W = Wide voltage (12–240V AC/DC), N = NPN trigger, P = PNP trigger, 1 = 1×SPDT, 2 = 2×SPDT. Control signal: NPN type connects S to A2; PNP type connects S to A1.

⚙️ Technical Specifications

🔌 Input

Input TerminalA1 – A2
Supply Voltage12–240V AC/DC
Power ConsumptionAC 3.5VA / DC 2.0W
Voltage Tolerance-15% ~ +10%

🎛️ Control Circuit

Control TerminalsA1–S (PNP) / A2–S (NPN)
Control Pulse Lengthmin. 25ms / max. unlimited
FunctionOff-Delay
Time Range0.1s – 100 days

⏱️ Time Circuit

Time SettingButton (digital)
Time Deviation0% – Digital Setting
Repeat Accuracy0.2%
Temperature Coefficient0.01%/°C (at 20°C)

🔌 Output

Contact (B1 series)1 × SPDT
Contact (B2 series)2 × SPDT
Rated Current16A @ 250V AC
Mechanical Life1×10⁷ operations
Electrical Life1×10⁵ operations

📐 Physical & Environmental

Dimensions18 × 90 × 64 mm
MountingDIN rail EN 60715
Protection DegreeIP40 (front) / IP10 (terminals)
Operating Temp.-20°C ~ +55°C
Storage Temp.-30°C ~ +70°C

📜 Standards & Certifications

ComplianceGB/T 14048.5, IEC 60947-5-1, EN 6812-1
Contact ConfigurationSPDT: 11(COM)-12(NC)-14(NO)
2nd pole: 21(COM)-22(NC)-24(NO)
Pollution Degree2
Max. Cable SizeAWG 13–20 / 0.4 N·m

📈 Function Diagram – Off-Delay Operation

FCT18-B Off-Delay Timer with Control Signal Function Diagram — timing sequence

• After power-on, output relay R closes (NO contact makes, NC breaks) and timing period T starts.
• At the end of the timing period T, the output relay R opens.
• Closing of the control signal S makes the output relay R close.
• Opening of S restarts the timing period T.
• After the duration T, the output relay R opens again.
This cycle repeats each time S toggles. Removing supply voltage resets the device.

🎬 See it in Action

🔧 Wiring & Terminal Layout

Terminal Identification

A1 — L / + (Supply) A2 — N / - (Supply) S — Control Signal 11 — COM 12 — NC 14 — NO 21 — COM (2nd pole) 22 — NC (2nd pole) 24 — NO (2nd pole)
⚠️ Safety Note: Keep the power supply disconnected during the entire installation process. Carefully check the wiring diagram and follow it correctly. Adhere to the specified voltage and current limits for each connection terminal.

NPN models (WN): Control signal between S and A2.
PNP models (WP): Control signal between S and A1.

FCT18-B Wiring and Terminal Layout Diagram

🛠️ Parameter Setting Guide

  1. Enter Parameter Setting Mode: Press and hold the button until the LED starts flashing. This indicates you have entered the configuration mode.
  2. Adjust Time Range & Fine Time: Use the button to set the desired time range (coarse) and fine time adjustment. The scale markings on the front panel guide your setting.
    💡 Note: When the green LED is ON during time range setting, add +5% to the value indicated on the scale for accurate timing.
  3. Confirm New Parameters: After adjusting to your desired values, press and hold the button until the LED stops flashing. The new parameters are now stored.
  4. Make Parameters Effective: After confirming parameters, you must power off and restart the device to activate the new settings.

🏭 Typical Applications

🏗️ Industrial Automation
Delayed stop for conveyors, assembly lines after process completion
⚙️ Motor Protection
Delayed disconnection to cool down or complete a cycle
💡 Lighting Control
Automatic off-delay for staircases, corridors, and parking lots
🌬️ HVAC Systems
Fan off-delay to purge residual heat or maintain circulation
🔋 Power Supply Protection
Off-delay to ensure safe shutdown sequence for sensitive equipment
🚨 Emergency Stop Circuits
Controlled delayed power-off for safe machinery shutdown

🔗 Related Products

Explore other time relays in the FCT18 series:

❓ Frequently Asked Questions

🔹 What is an Off-Delay relay and how does the control signal work?
An Off-Delay relay keeps its output closed when powered on and starts the timing cycle. The output opens only when the set time elapses. The control signal S can re-close the output and restart the timing, making it ideal for extending operation after a trigger signal disappears.
🔹 What is the difference between NPN (WN) and PNP (WP) models?
The trigger logic differs: NPN models (WN) require the control signal to connect S to A2 (sinking), while PNP models (WP) require the control signal to connect S to A1 (sourcing). Choose based on your PLC or control system output type.
🔹 Can this relay operate on both AC and DC supply?
Yes. The FCT18-B series accepts 12–240V AC or DC on terminals A1–A2, making it truly universal for global control panel designs.
🔹 How do I set a time value of exactly 30 seconds?
Enter parameter setting mode (long-press until LED flashes), set the coarse time range to the appropriate scale, then use fine time adjustment. Note: when the green LED is on during range setting, add 5% to the scale reading. Confirm by long-pressing until the LED stops flashing, then power-cycle the device.
🔹 What is the minimum control pulse length required?
The control signal pulse must be at least 25 milliseconds to trigger the timing cycle. There is no maximum limit — the signal can remain active indefinitely.
🔹 Is the output contact rated for inductive loads?
The SPDT contacts are rated for 16A @ 250V AC. For inductive loads (motors, solenoids, contactors), proper snubbing or derating is recommended to maximize contact life.

📞 Need a Quote or Technical Support?

Contact us today for pricing, bulk orders, or application assistance. We respond within 24 hours.

Get A Quote