Star-Delta Time Relay
for Motor Starting
Industrial-grade star-delta timer with digital setting, ultra-wide voltage range, and smooth transition for reduced inrush current in motor starting applications.
📋 Model & Ordering
| Model | Supply Voltage | Output Contact | Function | Time Range | Datasheet |
|---|---|---|---|---|---|
| FCT18-ST | 12–240V AC/DC | 2 × SPDT | Star-Delta | 0.1s – 40min | 📄 Download PDF |
💡 This is a dedicated Star-Delta timer with 2 SPDT outputs for star and delta contactor control. No external control signal (S) is required.
⚙️ Technical Specifications
🔌 Input
| Input Terminal | A1 – A2 |
| Supply Voltage | 12–240V AC/DC |
| Power Consumption | AC 3.5VA / DC 2.0W |
| Voltage Tolerance | -15% ~ +10% |
⏱️ Time Circuit
| Function | Star-Delta |
| Time Range (Star) | 0.1s – 40min |
| Time Setting | Button (digital) |
| Time Deviation | 0% – Digital Setting |
| Repeat Accuracy | 0.2% |
| Temperature Coefficient | 0.01%/°C (at 20°C) |
🔌 Output
| Contact | 2 × SPDT |
| Rated Current | 16A @ 250V AC |
| Mechanical Life | 1×10⁷ operations |
| Electrical Life | 1×10⁵ operations |
📐 Physical & Environmental
| Dimensions | 18 × 90 × 64 mm |
| Mounting | DIN rail EN 60715 |
| Protection Degree | IP40 (front) / IP10 (terminals) |
| Operating Temp. | -20°C ~ +55°C |
| Storage Temp. | -30°C ~ +70°C |
📜 Standards & Certifications
| Compliance | GB/T 14048.5, IEC 60947-5-1, EN 6812-1 |
| Contact Configuration | 11(COM)-12(NC)-14(NO) / 21(COM)-22(NC)-24(NO) |
| Pollution Degree | 2 |
| Max. Cable Size | AWG 13–20 / 0.4 N·m |
📈 Function Diagram – Star-Delta Operation
• After power-on, output R1 closes the star contactor and the main contactor, and timing T1 starts (star connection time period).
• At the end of T1, output R1 reverts to its initial state, opening the star contactor and starting the transition time T2.
• At the end of T2, output R2 closes, engaging the delta contactor for full-load run.
• This sequence ensures a smooth, controlled transition from star to delta, reducing mechanical and electrical stress.
🎬 See it in Action
🔧 Wiring & Terminal Layout
Terminal Identification
R1 controls the star contactor, R2 controls the delta contactor. The main contactor is typically wired in parallel with the supply.
🛠️ Parameter Setting Guide
- Enter Parameter Setting Mode: Press and hold the button until the LED starts flashing. This indicates you have entered the configuration mode.
-
Adjust Star Time (T1) & Fine Time: Use the button to set the desired star time (coarse) and fine time adjustment. The scale markings on the front panel guide your setting.
💡 Note: When the green LED is ON during time range setting, add +5% to the value indicated on the scale for accurate timing.
- Confirm New Parameters: After adjusting to your desired values, press and hold the button until the LED stops flashing. The new parameters are now stored.
- Make Parameters Effective: After confirming parameters, you must power off and restart the device to activate the new settings.
🏭 Typical Applications
Smooth star-delta transition to reduce inrush current and voltage dips
Soft start for water pumps to prevent water hammer and pipe stress
Reduce mechanical stress during compressor startup
Minimize voltage drops on fan startup in ventilation systems
Gradual acceleration to avoid belt slippage and mechanical shock
Reliable starting for large air handling units and chillers
🔗 Related Products
Explore other time relays in the FCT18 series:
❓ Frequently Asked Questions
📞 Need a Quote or Technical Support?
Contact us today for pricing, bulk orders, or application assistance. We respond within 24 hours.