Voltage Control Relay
Over & Under Voltage — Manual Reset
Precision single-phase voltage monitoring relay with independent overvoltage and undervoltage thresholds, adjustable time delay, and manual reset function — ideal for protecting sensitive equipment where automatic restart is not desired.
📋 Models & Ordering
| Model | Monitoring Voltage | Voltage Type | Reset Mode | Supply Voltage | Datasheet |
|---|---|---|---|---|---|
| FCV18-01A240 | 65–260V | AC | Manual | 12–240V AC/DC | 📄 Download PDF |
| FCV18-01A220 | 165–260V | AC | Manual | 12–240V AC/DC | 📄 Download PDF |
| FCV18-01A48 | 20–80V | AC | Manual | 12–240V AC/DC | 📄 Download PDF |
| FCV18-01D240 | 65–260V | DC | Manual | 12–240V AC/DC | 📄 Download PDF |
| FCV18-01D48 | 20–80V | DC | Manual | 12–240V AC/DC | 📄 Download PDF |
| FCV18-01D12 | 9–18V | DC | Manual | 12–240V AC/DC | 📄 Download PDF |
💡 Model selection guide: Choose A prefix for AC voltage monitoring, D prefix for DC voltage monitoring. The number indicates the nominal monitoring voltage range. All models share the same 12–240V AC/DC supply on A1-A2 terminals, manual reset function, and digital push-button parameter setting.
⚙️ Technical Specifications
🔌 Supply
| Supply Terminals | A1 – A2 |
| Supply Voltage | 12–240V AC/DC |
| Power Consumption | AC 3.5VA / DC 2.0W |
| Voltage Tolerance | -15% ~ +10% |
🛡️ Monitoring Function
| Function | Over & Under Voltage Protection |
| Reset Mode | Manual Reset |
| Monitoring Terminals | S1 – S2 |
| Setting Accuracy | 0% – Digital Setting |
| Measurement Accuracy | ≤1% / ±1V |
| Time Delay | Adjustable via button |
🔌 Output
| Contact | 1 × SPDT |
| Rated Current | 16A @ 250V AC |
| Mechanical Life | 1×10⁷ operations |
| Electrical Life | 1×10⁵ operations |
📐 Physical & Environmental
| Dimensions | 18 × 90 × 64 mm |
| Mounting | DIN rail EN 60715 |
| Protection Degree | IP40 (front) / IP10 (terminals) |
| Operating Temp. | -20°C ~ +55°C |
| Storage Temp. | -30°C ~ +70°C |
📜 Standards & Certifications
| Compliance | GB/T 14048.5, IEC 60947-5-1, EN 6812-1 |
| Contact Configuration | SPDT: 11(COM)-12(NC)-14(NO) |
| Pollution Degree | 2 |
| Max. Cable Size | AWG 13–20 / 0.4 N·m |
💡 Panel LED Indicators
| LED | Color | Status | Meaning |
|---|---|---|---|
| Un | Green | OFF | Supply voltage not applied |
| Un | Green | ON | Supply voltage applied |
| R | Red | OFF | NC (11-12) contact closed |
| R | Red | ON | NO (11-14) contact closed |
📈 Function Diagram – Overvoltage & Undervoltage Protection
• The relay monitors single-phase voltage via terminals S1–S2.
• When supply voltage A1-A2 is applied and the monitored voltage is within the set thresholds, the output relay R closes (NO contact 11-14 makes).
• If voltage goes above the overvoltage threshold, the output relay R opens after the set time delay to protect connected equipment.
• If voltage drops below the undervoltage threshold, the output relay R opens after the set time delay.
• Manual Reset: After a fault clears, the output relay remains open even when voltage returns to normal. The operator must either press and hold the button or cycle the supply power to reset the relay. This prevents automatic restart of machinery after a voltage event.
🎬 See it in Action
🔧 Wiring & Terminal Layout
Terminal Identification
Supply (A1–A2): Connect to 12–240V AC/DC. This powers the relay's internal electronics.
Monitoring (S1–S2): Connect the voltage to be monitored. For AC, polarity is not critical. For DC models, observe polarity.
Output (11-12-14): SPDT contact rated 16A @ 250V AC. Wire in series with the load contactor or protection circuit.
🛠️ Parameter Setting Guide
- Enter Parameter Setting Mode: Press and hold the button until the LED starts flashing. This indicates you have entered the configuration mode.
- Set Overvoltage Threshold (U>): Use the button to set the upper voltage limit. When the monitored voltage exceeds this value, the relay will trip after the time delay.
- Set Undervoltage Threshold (U<): Configure the lower voltage limit. When the monitored voltage drops below this value, the relay will trip after the time delay.
- Set Time Delay: Adjust the time delay from the available range. This delay applies before the output opens on voltage faults and before the initial closure on power-up.
- Confirm and Store: After all parameters are adjusted, press and hold the button until the LED stops flashing. The settings are stored and take effect after a power cycle.
🏭 Typical Applications
Prevents equipment damage from generator voltage excursions — manual reset ensures operator inspection
Protects CNC and precision machines where automatic restart after a fault is unsafe
Prevents lamp and ballast damage from sustained overvoltage conditions
Monitors DC battery voltage — protects against overcharge and deep discharge
Safeguards compressors and fan motors from voltage-related failures
Protects sensitive communication gear from DC supply voltage anomalies