Voltage Control Relay
Over & Under Voltage — Auto Reset
Precision single-phase voltage monitoring relay with independent overvoltage and undervoltage thresholds, adjustable hysteresis, time delay, and automatic reset — perfect for unattended protection of equipment against voltage anomalies.
📋 Models & Ordering
| Model | Monitoring Voltage | Voltage Type | Reset Mode | Supply Voltage | Datasheet |
|---|---|---|---|---|---|
| FCV18-02A240 | 65–260V | AC | Auto | 12–240V AC/DC | 📄 Download PDF |
| FCV18-02A220 | 165–260V | AC | Auto | 12–240V AC/DC | 📄 Download PDF |
| FCV18-02A48 | 20–80V | AC | Auto | 12–240V AC/DC | 📄 Download PDF |
| FCV18-02D240 | 65–260V | DC | Auto | 12–240V AC/DC | 📄 Download PDF |
| FCV18-02D48 | 20–80V | DC | Auto | 12–240V AC/DC | 📄 Download PDF |
| FCV18-02D12 | 9–18V | DC | Auto | 12–240V AC/DC | 📄 Download PDF |
💡 Model selection guide: A prefix = AC monitoring, D prefix = DC monitoring. The number indicates the nominal monitoring voltage range. All models share 12–240V AC/DC supply, auto reset, adjustable hysteresis, and digital push-button configuration.
⚙️ Technical Specifications
🔌 Supply
| Supply Terminals | A1 – A2 |
| Supply Voltage | 12–240V AC/DC |
| Power Consumption | AC 3.5VA / DC 2.0W |
| Voltage Tolerance | -15% ~ +10% |
🛡️ Monitoring Function
| Function | Over & Under Voltage Protection |
| Reset Mode | Auto Reset |
| Monitoring Terminals | S1 – S2 |
| Setting Accuracy | 0% – Digital Setting |
| Measurement Accuracy | ≤1% / ±1V |
| Hysteresis | Adjustable (1% – 2%) |
| Time Delay | Adjustable via button |
🔌 Output
| Contact | 1 × SPDT |
| Rated Current | 16A @ 250V AC |
| Mechanical Life | 1×10⁷ operations |
| Electrical Life | 1×10⁵ operations |
📐 Physical & Environmental
| Dimensions | 18 × 90 × 64 mm |
| Mounting | DIN rail EN 60715 |
| Protection Degree | IP40 (front) / IP10 (terminals) |
| Operating Temp. | -20°C ~ +55°C |
| Storage Temp. | -30°C ~ +70°C |
📜 Standards & Certifications
| Compliance | GB/T 14048.5, IEC 60947-5-1, EN 6812-1 |
| Contact Configuration | SPDT: 11(COM)-12(NC)-14(NO) |
| Pollution Degree | 2 |
| Max. Cable Size | AWG 13–20 / 0.4 N·m |
💡 Panel LED Indicators
| LED | Color | Status | Meaning |
|---|---|---|---|
| Un | Green | OFF | Supply voltage not applied |
| Un | Green | ON | Supply voltage applied |
| R | Red | OFF | NC (11-12) contact closed |
| R | Red | ON | NO (11-14) contact closed |
📈 Function Diagram – Overvoltage & Undervoltage Protection (Auto Reset)
• The relay monitors single-phase voltage via terminals S1–S2.
• When supply voltage A1-A2 is applied and the monitored voltage is within the set thresholds, the output relay R closes (NO contact 11-14 makes).
• If voltage goes above the overvoltage threshold, the output relay R opens after the set time delay. It will re-close when voltage drops below the overvoltage reset value (determined by the set hysteresis percentage).
• If voltage drops below the undervoltage threshold, the output relay R opens after the set time delay. It will re-close when voltage rises above the undervoltage reset value.
• Auto Reset: No manual intervention is required. The relay automatically re-energizes when the monitored voltage returns to within the reset window, making it ideal for unattended equipment protection.
🎬 See it in Action
🔧 Wiring & Terminal Layout
Terminal Identification
Supply (A1–A2): Connect to 12–240V AC/DC to power the relay.
Monitoring (S1–S2): Connect the circuit whose voltage is to be monitored. For DC models, observe correct polarity.
Output (11-12-14): SPDT contact rated 16A @ 250V AC. Wire in series with the load or alarm circuit.
🛠️ Parameter Setting Guide
- Enter Parameter Setting Mode: Press and hold the button until the LED starts flashing. This indicates you have entered the configuration mode.
- Set Overvoltage Threshold (U>): Adjust the upper trip voltage. When the monitored voltage exceeds this value, the relay will open after the time delay.
- Set Undervoltage Threshold (U<): Adjust the lower trip voltage. When the monitored voltage drops below this value, the relay will open after the time delay.
- Set Hysteresis: Choose the hysteresis percentage (typically 1% or 2%). This determines the reset voltage: overvoltage reset = U> × (1 - hysteresis%); undervoltage reset = U< × (1 + hysteresis%). This prevents oscillation around the trip points.
- Set Time Delay: Adjust the delay before tripping on voltage faults. This also applies to the initial closing delay upon power-up.
- Confirm and Store: After all parameters are adjusted, press and hold the button until the LED stops flashing. The settings are stored and take effect immediately.
🏭 Typical Applications
Automatically protects equipment from voltage swings without operator intervention
Prevents motor burnout from under/over voltage with automatic restart when supply recovers
Safeguards lamps and ballasts from overvoltage while automatically restoring after correction
Monitors battery voltage in solar/wind installations with hysteresis for charge controller staging
Maintains process uptime by allowing automatic recovery from transient voltage events
Protects sensitive communication gear from DC supply anomalies with seamless auto-reset